Permit Number: T18CM07565
Parcel: 10701040B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM07565
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2018 MCASTRO2 ZONING REVIEW Approved
09/24/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating/cooling load calculations for the new heat pumps.
2. Provide a 4" diameter exhaust vent for the clothes dryer.
09/24/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Provide certificate of compliance or electrical lighting calculations for verification in accordance with IECC C405.2
2. Specfify the amperage rating of the new electrical panel.
09/24/2018 JOHN VAN WINKLE ENGINEERING REVIEW Approved
09/24/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. The water dispenser controls reqyured to be ADA compliant for operation at the sink. Please verify.
09/24/2018 ROBERT SHERRY WATER REVIEW Completed
09/24/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify the presence of a water pressure regulator (75-85 PSI).
2. Verify the valave handle on the water dispenser is listed as being accessible.
3. Provide 3" horizontal waste for clothes washer & sink.
09/24/2018 JVINCEN1 FIRE REVIEW Approved
09/25/2018 SVALENZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review