Permit Number: T18CM07189
Parcel: 117120310

Address:
1 E CONGRESS ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM07189
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2018 ROBERT SHERRY WATER REVIEW Completed
09/12/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show that the new storefront meets the requirements of Section C402, IECC 2012.
09/12/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide note on plans: Security grille shall be openable from the inside without the use of a key or special knowledge or effort when the space is occupied.
2. Provide note on plans: The grilles shall remain secured in the full open position position when the space is occupied.
3. The occupant load factor for grade floor mercantile occupancy is 30, not 60 per IBC TABLE 1004.1.2. Provide a revised occupant load.
4. Specify the valuation for the project.
4. Identify the required exits from the space. Where 2 or more exits are required, not more than one-half of the exits are allowed to have security grilles.
5. List the 2012 International Building Code on the adopted codes, not the IRC.
09/12/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/13/2018 MARTIN BROWN FIRE REVIEW Reqs Change Please add note indicating security grill will meet the requirements of section 1010.1.4.5 of the 2018 International Fire Code.
09/13/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed
09/14/2018 QJONES1 ENGINEERING REVIEW Reqs Change
09/14/2018 QJONES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
09/14/2018 QJONES1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/14/2018 QJONES1 APPROVAL SHELF Completed
09/14/2018 QJONES1 OUT TO CUSTOMER Completed
09/14/2018 QJONES1 REJECT SHELF Completed