Permit Number: T18CM07123
Parcel: 13824083A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T18CM07123
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2019 MARTIN BROWN FIRE REVIEW Approved
06/06/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A.1; Building Code Analysis (General Building Summary): Because this is a shell only permit, no determination for occupancy classification, occupant load, allowable building area, or required plumbing fixtures will be reviewed. However, it would be advisable to research those issues before applying for the build-out of the structure. For example, the General Building Summary indicates a Factory (F-1) occupancy classification, while the Building Code Analysis indicates Warehouse. This will produce totally different occupant loads and could affect other design aspects.
2. Sheet A.1: The Title Sheet indicates a pre-fabricated building shell in several locations. This is a pre-engineered metal building that is site fabricated. Please revise.
3. Sheet A.2; Floor Plan: A diagonal line in the building indicates "192 LF Travel Distance to Exit Fire Sprinkler Structure". The IBC Section 1007.1.1 indicates exits must be placed a distance apart not less than 1/2 of the length of the maximum diagonal dimension of the building. Please indicate the building exits on the Floor Plan, and verify they meet that code requirement.
4. Sheet S.1; Metal Building Structural Calculations: Per the IBC Section 107.3.4, the registered design professional in responsible charge is responsible for reviewing and coordinating submittal documents prepared by others. Mr. Florez should submit a signed, sealed letter indicating he has reviewed and coordinated the calculations and drawings for the metal building, and all requirements of that Section have been met.
5. General: Please provide the Special Inspection Certificate with Parts A and B completed.
6. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
06/07/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/07/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the material to be used for water distribution: copper or CPVC? Reference: Section 107.2.1, IBC 2012.
2. Specify the insulation for the hot water distribution pipe. [Initial comment: If the proposed service hot water piping is running under the slab, state how it is to be insulated. Reference: Section C404.5, IECC 2012.
06/07/2019 ROBERT SHERRY WATER REVIEW Completed
06/21/2019 LOREN MAKUS ENGINEERING REVIEW Needs Review DP19-0051 must be approved first.
06/27/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet E3. There is an equipment schedule showing various electrical equipment and power requirements. Provide complete electrical floorplans with the locations of the equipment. Also include any other power and lighting, panel schedules. Or if the scope of electrical work only includes the service and grounding, indicate this with a note on the plans.
Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
07/02/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM7123 - New Building (Industrial / General Manufacturing)
Building Plan Review (2nd Review) S&R Cabinetry Builders
6721 S Renaissance Drive - 1-1 Zoning - Related to DP19-0051

TRANSMITTAL DATE: July 2, 2019

DUE DATE: June 28, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has done a cursory review of the building plans and a comparison for consistency with the current version of the unapproved DP. While the cursory review did yield an indication that the building plans are consistent with what has been proposed and drawn on the DP with the exception listed for the building height (that has been submitted for review) zoning cannot approve the building plans at this time.

While the building footprint is consistent with the footprint on the DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc.) zoning is requesting that the Building plans or the DP plans are revised to list the correct building height measured from design grade (adjacent ground) to the top of the roof Ridge. Per the DP the maximum height is listed as 16 feet and the building plans dimensioned the building height as 20 feet to the top of the ridge of the roof.


2. COMMENT: Zoning will review the building plans on the next submittal to assure consistency with the DP. If any changes are necessary to the building plans due to plan review comments that affect zoning requirements the DP will have to be revised to reflect the changes. Once the DP is approved by all reviewers and the building plans are approved by the Commercial Plans reviewers zoning can approve the building plans.


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans

Final Status

Task End Date Reviewer's Name Type of Review Description
07/10/2019 AVAUGHN1 APPROVAL SHELF Completed
07/10/2019 AVAUGHN1 OUT TO CUSTOMER Completed
07/10/2019 PMARTIN1 REJECT SHELF Completed