Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2019 MARTIN BROWN FIRE REVIEW Reqs Change Please provide exiting plan showing travel distances to exits.
Please indicate on plans approximate proposed location of fire service underground.
Add note indicating fire sprinklers, fire alarms (monitoring), and the service underground piping will be a deferred submittal through the fire department.
Also, be advised that sprinklers are not a fire department requirement, but mandated by the International Fire Code, which has been adopted by the city of Tucson.
04/22/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/23/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the size of the proposed water meter for this building.
2. Specify the slope of the building drain and the building sewer. Reference: Table 704.1, IPC 2012.
3. Provide a cleanout in the building sewer prior to entering the right-of-way. Reference: Pima County Standard Detail RWRD 401, 2015.
4. The rim elevation of the next upstream sanitary manhole (2473.35') is higher than the proposed first floor elevation of the proposed shell building (2473.00'). Provide a backwater valve when future plumbing activities take place. Reference: Section 715.1, IPC 2012, as amended by the City of Tucson.
5. If the proposed service hot water piping is running under the slab, state how it is to be insulated. Reference: Section C404.5, IECC 2012.
04/23/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/23/2019 ROBERT SHERRY WATER REVIEW Reqs Change Show the location of the reduced pressure backflow assembly on the drawings; indicate the size of the assembly. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf.
05/01/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM7123 - New Building (Industrial / General Manufacturing)
Building Plan Review (1st Review) S&R Cabinetry Builders
6721 S Renaissance Drive - 1-1 Zoning - Related to DP19-0051

TRANSMITTAL DATE: May 1, 2019

DUE DATE: May 7, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has done a cursory review of the building plans and a comparison for consistency with the current version of the unapproved DP. While the cursory review did yield an indication that the building plans are consistent with what has been proposed and drawn on the DP with the exception listed for the building height (that has been submitted for review) zoning cannot approve the building plans at this time.

While the building footprint is consistent with the footprint on the DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc.) zoning is requesting that the Building plans or the DP plans are revised to list the correct building height measured from design grade (adjacent ground) to the top of the roof Ridge. Per the DP the maximum height is listed as 16 feet and the building plans dimensioned the building height as 20 feet to the top of the ridge of the roof.


2. COMMENT: Zoning will review the building plans on the next submittal to assure consistency with the DP. If any changes are necessary to the building plans due to plan review comments that affect zoning requirements the DP will have to be revised to reflect the changes. Once the DP is approved by all reviewers and the building plans are approved by the Commercial Plans reviewers zoning can approve the building plans.


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans
05/02/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide complete electrical plans designed and sealed by an Electrical Engineer registered in Arizona. Electrical systems exceeding 400 amps require an electrical Engineered Design and seal.
Ref; City of Tucson Commercial Plan Submittal requirements, ARS R4-30-302.
05/07/2019 LOREN MAKUS ENGINEERING REVIEW Reqs Change Development Package DP19-0051 must be approved first.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/31/2019 AVAUGHN1 OUT TO CUSTOMER Completed