| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/06/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref; Plan Sheet E4.0. One Line Diagram. (a) Insert the correct keyed note shown for the service conductors between the existing Term Can and the new 400 amp Meter and CT Can. Also provide grounded conductors (neutrals) with the ungrounded conductors to terminate in the new service disconnect. NEC 250.24. (b) Indicate the size and type of the GEC bonding conductor between the existing and new service. (c) Provide a grounding detail for the new 75kva transformer. (d) The OCPD (200 amps) is over sized for the #2 feeders for the 75kva transformer. NEC 240.4 (e) Provide disconnecting means with overcurrent protection within 25' of the 75kva transformer to protect the secondary conductors feeding panel LP1A. NEC 240.15, 240.21, 450.14. (f) Indicate fuse sizes and types and AIC rating for the new service disconnect. (g) Indicate AIC ratings for the panels. Ref; 2012 IBC 107.2.1, 2011 NEC. City of Tucson Commercial Plan Submittal Requirements (Electrical). |