Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T18CM06804
Parcel: 10701040B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM06804
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/06/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Plan Sheet E4.0. One Line Diagram.
(a) Insert the correct keyed note shown for the service conductors between the existing Term Can and the new 400 amp Meter and CT Can. Also provide grounded conductors (neutrals) with the ungrounded conductors to terminate in the new service disconnect. NEC 250.24.
(b) Indicate the size and type of the GEC bonding conductor between the existing and new service.
(c) Provide a grounding detail for the new 75kva transformer.
(d) The OCPD (200 amps) is over sized for the #2 feeders for the 75kva transformer. NEC 240.4
(e) Provide disconnecting means with overcurrent protection within 25' of the 75kva transformer to protect the secondary conductors feeding panel LP1A. NEC 240.15, 240.21, 450.14.
(f) Indicate fuse sizes and types and AIC rating for the new service disconnect.
(g) Indicate AIC ratings for the panels.
Ref; 2012 IBC 107.2.1, 2011 NEC. City of Tucson Commercial Plan Submittal Requirements (Electrical).