Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM06804
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/29/2018 | GPERU1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/29/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Approved | |
| 08/29/2018 | EHAMBLI1 | ZONING | REVIEW | Approved | |
| 08/29/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/30/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Approved | Please provide emergency egress lighting for the new office areas. A1 |
| 09/04/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 09/04/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 09/04/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/05/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please re- print plan sheet E4.0. the one line diagram is not legible, print to light. Also enlarge the IECC comcheck on plan sheet E0.1 to a minimum text size of 3/32". Ref 2012 IBC 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal Requirements. |