Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM06526
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/21/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
08/30/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S1; General Structural Notes (Seismic Loads): The seismic design category is listed as A, B, C, or D. Does this imply the design is adequate for all of these categories, or should this note indicate just one category? Please clarify. 2. Sheet S1; General Structural Notes (Foundations): The note for spread footings indicates the design is based on the IBC Section 1806, then indicates to refer to the soils report. In addition, the note indicates a soils engineer will inspect foundation excavations. Please clarify. 3. General: Please provide written responses to all review comments. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/06/2018 | SVALENZ1 | OUT TO CUSTOMER | Completed |