| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/29/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/13/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref; line diagrams. The feeder from the 160 kva transformer to the interconnection is undersized for the load (443 amps) and overcurrent protection fuse rating of the AC Disconnect (550 amp fuses). Parallel 250 kcmil cu has a current carrying capacity of 410 amps per table 310.159B) (16), 75 deg. NEC 240.4, 240.6 Ref 2011 NEC |