Permit Number: T18CM06412
Parcel: 12218274B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM06412
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/13/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; line diagrams. The feeder from the 160 kva transformer to the interconnection is undersized for the load (443 amps) and overcurrent protection fuse rating of the AC Disconnect (550 amp fuses). Parallel 250 kcmil cu has a current carrying capacity of 410 amps per table 310.159B) (16), 75 deg. NEC 240.4, 240.6
Ref 2011 NEC

Final Status

Task End Date Reviewer's Name Type of Review Description
09/20/2018 SVALENZ1 OUT TO CUSTOMER Completed