Permit: T18CM06412
Permit Details
Apply Date:
08/15/2018
Applicant:
TECHNICIANS FOR SUSTAINABILITY INC
Description:
COMMERCIAL SOLAR
Contractors:
- TECHNICIANS FOR SUSTAINABILITY INC
Permit Reviews
Permit Number - T18CM06412
Permit Status: Final
Permit Description: COMMERCIAL SOLAR
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/15/2018 | PLANS OK TO SUBMIT - COMM | 08/15/2018 | COMPLETED |
| 08/15/2018 | COMMERCIAL - BLDG/FIRE/ZONING/ENG | 09/20/2018 | COMPLETED |
| 09/20/2018 | COMMERCIAL - BLDG/FIRE/ZONING/ENG | 09/20/2018 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T18CM06412
Permit Status: Final
Permit Description: COMMERCIAL SOLAR
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/15/2018 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T18CM06412
Permit Description: COMMERCIAL SOLAR
Total Completed Inspections - 11
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2019 | ELECTRIC - UNDERGROUND | ESTEVENS | Approved | FROM R1, R2 AND P1 TO TRANSFORMER ON NORTH SIDE OF BUILDING. |
| 01/22/2019 | ELECTRIC - INTERMEDIATE | BSTEVENS | Approved | CLEARED DGL NEW 160KVA TRANSFORMER, 1200AMP SOLAR CT CABINET/METER, 600AMP PV UTILITY DISCONNECT, PARALLEL FEEDS #250, GRND AND NEUTRAL #2AWG. ALL EQUIPMENT BONDED. PV LINE TAP ON EXISTING 800AMP BUS BAR. HI-POT PROVIDED ON PV SOLAR CONDUCTORS AND APPROVED |
| 01/22/2019 | ELECTRIC - OUTDOOR LIGHTING | BSTEVENS | Approved | |
| 01/22/2019 | ELECTRIC - FINAL | BSTEVENS | Approved | |
| 01/22/2019 | ELECTRIC - UFER | BSTEVENS | Approved | |
| 01/22/2019 | EXCAVATION/LAYOUT REBAR & ZON | BSTEVENS | Approved | |
| 01/22/2019 | BUILDING - FINAL | BSTEVENS | Approved | |
| 01/22/2019 | FRAMING | BSTEVENS | Approved | |
| 01/22/2019 | ROOF NAILING | BSTEVENS | Approved | |
| 01/23/2019 | OUTDOOR LIGHTING FINAL | BSTEVENS | Approved | |
| 01/24/2019 | TEP CLEARANCE - AM | BSTEVENS | Approved | DGL/DGC |