Permit Number: T18CM06408
Parcel: 117160130

Address:
35 E TOOLE AV

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T18CM06408
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/12/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
11/12/2019 SARAH MEGGISON ZONING REVIEW Approved
11/12/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify what appear to be changes in the capacities of FC-11 and FC-12 from 4-tons to 5-tons. If changed, provide the load calculations.
11/12/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/12/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the hot water piping to P-1a so that the distance from the hot water source to the lavatory is 2-feet or less.