Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T18CM06408
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/12/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/12/2019 | SARAH MEGGISON | ZONING | REVIEW | Approved | |
11/12/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Clarify what appear to be changes in the capacities of FC-11 and FC-12 from 4-tons to 5-tons. If changed, provide the load calculations. |
11/12/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/12/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the hot water piping to P-1a so that the distance from the hot water source to the lavatory is 2-feet or less. |