Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T18CM06408
Parcel: 117160130

Address:
35 E TOOLE AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM06408
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 10; Sheet A2; Floor Plan: The IBC Section 2902.2 requires men and women plumbing fixtures to be in separate facilities. This requires the two water closets and the two lavatories for each sex to be physically separated from the other sex. This plan indicates all four water closets and all four lavatories in the same space. This plan does not meet the current code requirement. Please revise the drawing, or you may appeal the building official for this condition.
2. Previous Comment 13; Sheet A4; Floor Plan: Per the IBC Table 1021.2(2), the exit access travel distance must be indicated on the plan, including the distance up the stair to the exit door. The maximum allowable travel distance to the single exit is 75'. Please provide the path and the travel distance on the plan.
3. Sheet A4; Section 3: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the section verbiage.
4. Previous Comment 16; Sheet A5; Plan: The symbols in the restrooms have not been removed per the response letter. Please verify.
5. Sheet A8; Key Notes: Notes 2 and 9 were not located on the elevations. Please verify.
6. General: Please provide written responses to all review comments.
11/07/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
11/07/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed