Permit Number: T18CM06339
Parcel: 14002010A

Review Status: Active

Review Details: COMMERCIAL - NEW

Permit Number - T18CM06339
Review Name: COMMERCIAL - NEW
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2018 JVINCEN1 FIRE REVIEW Approved
08/27/2018 CLAYTON TREVILLYAN PLUMBING-COMMERCIAL REVIEW Passed
08/27/2018 CLAYTON TREVILLYAN ELECTRICAL-COMMERCIAL REVIEW Passed
08/27/2018 LMAKUS1 ZONING REVIEW Reqs Change Plans are stamped preliminary. Provide sealed plans.
08/27/2018 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T18CM05882, 6337 and 6339 - Plan Review Comments
Reviewer: Chris Anderson, August 23, 2018
1. Provide structural calculations sealed by the foundation engineer of record, Adam Redd, for foundations. Foundation review will be based on the structural calculation shown they are received. Ref. IBC 107.2.1
2. There appears to be no foundation plan for the smaller building U18SO0121A (T18CM06337).
3. Submit geotechnical reports(s) that the foundation designs were based on. Ref. 2012 IBC 107.2.1
4. No connection details are included in the metal building drawing sets and the headings such as "MZH04 Beams to RF Rafter" in the structural calculations do not correspond top member designations on the roof framing plans and sections. Either revise the roof plans or provided key plans in the structural calculation packages with the column, girder, beam and rafter with component marker that correspond to marker in the structural calculations o that drawings can be reviewed against the calculations.
08/27/2018 CTREVIL1 WATER REVIEW Passed
08/27/2018 CLAYTON TREVILLYAN MECHANICAL-COMMERCIAL REVIEW Passed
08/27/2018 LOREN MAKUS ENGINEERING REVIEW Approved
08/27/2018 CTREVIL1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/29/2018 AVAUGHN1 OUT TO CUSTOMER Completed
08/14/2018 ANY REJECT SHELF RECEIVED