Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM06314
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/15/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/31/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the discharge from the dishmachine will be 140 degrees Fahrenheit or less. Reference: Section701.7, IPC 2012. |
| 08/31/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/04/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide structural calculations and details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2012. 2. Provide an auxiliary or secondary condensate drain system for the fan coil units. Reference: Section 307.2.3, IMC 2012. 3. Provide the listing information, dimensions, weight, installation requirements and operating data (e.g. exhaust and make-up airflow rates) for the proposed Type I grease hood. Reference: Section 107.2.1, IBC 2012. 4. Show that the proposed utility exhaust unit complies with the requirements of Section 506.5, IMC 2012. 5. Verify that the proposed Type I hood is equipped to automatically start the hood exhaust fan when cooking operations commence. Reference: Section 507.2.1.1, IMC 2012. 6. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012. 7. Show that the hood installation complies with Section 507.9, IMC 2012 for clearances. 8. The mechanical plan shows a high-velocity diffuser in close proximity to the face of the Type I hood. Verify that the location and type of air outlet complies with the hood manufacturer's installation instructions and does not reduce the effectiveness of the exhaust system. Reference: Sections 304.1 and 508.1, IMC 2012. |
| 09/12/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |