Permit Number: T18CM05587
Parcel: 14029200A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM05587
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/03/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/04/2018 SVALENZ1 ZONING REVIEW Needs Review
10/04/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. As per the previous comment for the conduit and feeder schedule involving the ATS. The conduit and feeder schedule was not revised as stated in the response.
Ref; 2012 IBC sec 107.2.1, 2011 NEC
10/04/2018 SVALENZ1 ENGINEERING REVIEW Needs Review