Review Details: 3RD PARTY REVIEW - COMMERCIAL

Permit Number - T18CM05269
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2018 MARTIN BROWN FIRE REVIEW Reqs Change Round up when calculating occupant loads.
No exits signs indicated on plans.
Exiting through office not allowed. Revise cover sheet.
Remaining two exits do not appear to be required 1/2 the diagonal distance apart (non-sprinklered building).
Corridors may need to be 1 hour rated. Verify with building code examiner.
07/23/2018 ROBERT SHERRY WATER REVIEW Completed
07/26/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM05269 - New Building (Expansion to Existing Building)
Building Plan Review (1st Review) Pinpointe Accounting Services
7333 E. Tanque Verde Road - C-1 Zoning

TRANSMITTAL DATE: July 25, 2018

DUE DATE: August 2, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Zoning has reviewed the building plans for compliance with the approved TP/DP S04-032. While the building are in compliance with the approved TP/DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc.) zoning cannot approve the building plans until the 3rd Party and PDSD Commercial Plans reviewers have approved the building plans.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP. (Include a copy of the approved and PDSD stamped version of the DP with the next building submittal.)

3. COMMENT: If any changes are necessary, due to the 3rd Party or PDSD Commercial Plan Reviewer's comments that affect or change the building footprint, height, or square footage, the DP will need to be updated prior to approval of the building plans by Zoning.

4. COMMENT: Prior to approval of the building plans by zoning the parcels must be combined. A Pima County Assessor's Parcel Tax combination process can be processed through the Pima County Assessor's Office. Contact the Pima County for the requirements of the parcel tax combo. Copies of the "Processed" parcel tax combo forms shall be provided with the next submittal.

5. COMMENT: Once the plans have been reviewed and approved by the 3rd Party and PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP and the Parcel combo has been processed, the building plans can be approved by zoning.


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Building plans and Copies of the Parcel Combo
07/30/2018 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T18CM05269

1) Engineering has reviewed the building plans and they appear to be in conformance with the approved TP/DP S04-032. Engineering cannot approve the plans at this time as they are still in 3rd party commercial review
2) Engineering can conduct an over the counter review/approval once any outstanding review comments have been addressed and a new work flow opened. Call or Email to schedule

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
08/14/2018 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
08/14/2018 STANTEC 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/17/2018 AVAUGHN1 OUT TO CUSTOMER Completed
08/17/2018 AVAUGHN1 REJECT SHELF Completed