Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM05260
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2019 | AMARTIN1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 07/06/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 07/06/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/06/2018 | EHAMBLI1 | ENGINEERING | REVIEW | Passed | |
| 07/06/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide an enlarged floor plan of the ADA restroom; show maneuvering clearances around plumbing fixtures and clear area for water closet. 2. Provide attachement details of walls to the roof/ceiling and floor. 3. Provide plumbing fixture calculation for tenant build out; specify if existing restrooms used for TI and distance to existing restroom. |
| 07/06/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/06/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 07/06/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/06/2018 | EHAMBLI1 | ZONING | REVIEW | Approved |