Permit Number: T18CM04952
Parcel: 14032003B

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T18CM04952
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2018 MARTIN BROWN FIRE REVIEW Approved
07/03/2018 ROBERT SHERRY BUILDING-COMMERCIAL REVIEW Reqs Change Provide structural calculations for the masonry enclosure. Reference: Section 107.2.1, IBC 2012.
07/11/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Show the locations of the Tech Luminaires, Timer, and receptacle on the plans.
#2. Indicate how (wiring methods) the wiring for the existing light pole is to be re- routed to the new pole location.
#3. Provide a one line diagram of the electrical service and associated downstream equipment. Include, voltage and phase, amp rating, fuse sizes and types, load calcs, available fault current at the service, and the required AIC rating of the equipment.
#4. Ref; Plan Sheets E3, E4.
(a) The Grounding Electrode conductor (GEC) should be terminated in the Main Service Disconnect. Not the meter enclosure. NEC 250.24c.
(b) Indicate the size and type (cu, al) of the GEC run to the electrical service.
(c) The wall mount detail only shows one ground rod used to ground the electrical service. Provide 2 as required per NEC 250 .53A2, or show the GEC tied in with the grounding grid.
(d) Show the feeder number of conductors in each run, sizes and types for all feeders and branch circuits. Or provide a feeder schedule.
#5. Provide full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd.
Ref; 2012 IBC sec 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.
08/09/2018 SVALENZ1 COMMUNICATIONS REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/09/2018 SVALENZ1 OUT TO CUSTOMER Completed