Permit Number: T18CM04910
Parcel: 140133120

Address:
2353 E BANTAM RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM04910
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2018 MARTIN BROWN FIRE REVIEW Approved
07/10/2018 ERIC NEWCOMB ELECTRICAL-COMMERCIAL REVIEW Reqs Change PV4.0 Indicate the size of the bonding jumper from the neutral lug to the CT CABINET.
NOTICE FOR INSPECTOR: The 3-line drawing shows a supply-side connection for the photovoltaic system. A field inspection by an NRTL to RE-LIST the Sevice equipment may be necessary after the supply side tap is performed.
07/10/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Approv-Cond 1. Designate specific qualified individuals for the Special Inspections required for this project. IBC 1704.1

Final Status

Task End Date Reviewer's Name Type of Review Description
08/09/2018 AVAUGHN1 OUT TO CUSTOMER Completed
08/09/2018 AVAUGHN1 REJECT SHELF Completed