Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T18CM04817
Parcel: 10503002B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM04817
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. The construction type for the building is listed as Type III-A which requires that exterior walls be constructed of noncombustible materials. Keynote W1 on sheet A1.0 indicates 2x wood studs which would not be allowed on III-A construction type. Please correct. IBC 602.3
2. Specify the size and spacing of partition studs. IBC 107.2.1
3. An additional smoke detector is required in the hallway outside of the bedroom. IBC 420.5
06/20/2018 AHINES2 OIP REVIEW Passed
06/20/2018 AHINES2 ENGINEERING REVIEW Passed
06/20/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/20/2018 MARTIN BROWN FIRE REVIEW Approved
06/20/2018 ALEXANDRA HINES ZONING REVIEW Approved
06/21/2018 LPEREZ2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/21/2018 LPEREZ2 OUT TO CUSTOMER Completed