Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM04817
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/20/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. The construction type for the building is listed as Type III-A which requires that exterior walls be constructed of noncombustible materials. Keynote W1 on sheet A1.0 indicates 2x wood studs which would not be allowed on III-A construction type. Please correct. IBC 602.3 2. Specify the size and spacing of partition studs. IBC 107.2.1 3. An additional smoke detector is required in the hallway outside of the bedroom. IBC 420.5 |
06/20/2018 | AHINES2 | OIP | REVIEW | Passed | |
06/20/2018 | AHINES2 | ENGINEERING | REVIEW | Passed | |
06/20/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/20/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
06/20/2018 | ALEXANDRA HINES | ZONING | REVIEW | Approved | |
06/21/2018 | LPEREZ2 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/21/2018 | LPEREZ2 | OUT TO CUSTOMER | Completed |