Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T18CM04776
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/29/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G100; Egress Plan: Per the IBC Section 1016.3, the exit access travel distance shall be measured along horizontal and vertical travel to the exit. Please revise the diagonal distance measurements on this plan to meet the code requirements. 2. Sheet G100; Code Compliance: The second bullet point in Chapter 7 indicates a 2 hour minimum fire wall separating the new building from an existing building on the west. Sheet G001 (party wall) indicates the existing building is industrial use. Please indicate on Sheet G100 a note if the existing building is S-1 or S-2 (makes a difference in Table 706.4). 3. Sheet S1.0; Foundation Plan Keynote: Note 1 was not located on this plan. Please verify. 4. Sheet S1.0; Foundation Plan Keynote: At Note 3, please add a reference to Detail 109/S3.0 for a stepped footing. 5. Sheet S1.0 (Foundation Plan); Structural Calculations: No structural calculations were located for the steel tube column (C1 on Sheet S1.0). Please provide. 6. Sheet S1.0; Foundation Plan: Please provide a detail cut on the plan for Detail 108. 7. Sheet S2.0; Roof Framing Plan Keynote: Notes 1 and 4 were not located on this plan. Please verify. 8. Sheet S2.0; Roof Framing Plan: Please add a note to this sheet indicating to see Sheet S0.2 for the masonry lintel schedule. 9. Sheet S3.0; Details 101 and 107: Note 6 indicates the top of footing elevation (see plan). Should this note be indicated in Note 9 to see the foundation plan for the top of slab? No top of footing was located. 10. Sheet S3.0; Detail 105: Note 1 indicates the column is per the metal building manufacturer. However, on Sheet S1.0, the column sizes are indicated in the column schedule. Please clarify. 11. Structural Calculations (Lateral Analysis); Sheet S2.0 (Roof Framing Plan Keynote): The structural calculations indicate a plywood roof diaphragm, while the Note 5 indicates metal deck, and Note 4 indicates roof x-bracing. Please clarify. 12. Structural Calculations (CMU Walls); Sheet S2.0 (Roof Framing Plan): The structural calculations indicate a glu-lam beam bearing on the masonry wall, while the Roof Framing Plan indicates steel beams. Please verify. 13. Sheet A100; Floor Plan: The masonry wall X-1 is indicated on Grid 4 (interior wall), and shows up on the Exterior Wall Schedule. Please coordinate. 14. Sheet A100; Exterior Wall Schedule: There was no exterior wall X2 located on the plan. Please verify. 15. Sheet A101; Enlarged Restroom Plan: The clear floor space indicated at the lavatories shows a 24' x 48" space, while the ICC/ANSI Figure 305.3 requires 30" x 48". Please revise. 16. Sheet A101; Accessible Clearances: For the grab bars at the rear wall of the water closet, remove the 12" maximum dimension from the side wall to the end of the horizontal grab bar. See the ICC/ANSI Figure 604.5.2. 17. General: Please provide written responses to all review comments. |
| 06/29/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 07/06/2018 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/06/2018 | FRODRIG2 | WATER | REVIEW | Approved | |
| 07/06/2018 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/06/2018 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/12/2018 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T18CM04776- New Storage Building - Ref. DP15-0166 Building Plan Review (1st Review) 516 W. Lester Street - I-1 Zoning TRANSMITTAL DATE: July 12, 2018 DUE DATE: July 18, 2018 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the Building Plans for the Lester Storage building but cannot approve them at this time. While the building footprint is consistent with the approved version of the DP as it relates to the zoning review purview (Building footprint, Height, square footage that is under review zoning cannot approve the building plans at this time PDSD Commercial Plans reviewers have approved the building plans. Please show on the plans where the long term bicycle parking is proposed. 2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP. 3. COMMENT: If any changes are necessary, due to the PDSD Commercial Plan Reviewer's comments that affect or change the building footprint, height, or square footage, the DP will need to be updated prior to approval of the building plans by Zoning. 4. COMMENT: Once the plans have been reviewed and approved by the PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Building plans |
| 07/18/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | T18CM04776 1) The approved development plan shows a series of scuppers from the building through the sidewalk and into the parking lot. There should be associated roof drains that feed into the scuppers. Please show on the building plans the location of any proposed roof drains and coordinate to make sure they drain through scuppers as needed. Reference City of Tucson Technical Standards Manual section 7-01.4.1.E. 2) Engineering can conduct an over the counter review once the above comment and other outstanding department comments have been addressed John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov 520-837-5007 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/06/2018 | SVALENZ1 | OUT TO CUSTOMER | Completed |