Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM04532
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/11/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Show the location on the new Temporary service 'A' and downstream associated equipment on the site plan. Ref: City of Tucson, Commercial Plan Submittal Requirements, 2012 IBC sec 107.2.1, 2011 NEC. |
06/14/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Per the IBC Table 602, the new trailer must be located a minimum distance of 10 feet from the property line. The exterior wall will then require no fire resistance rating. The trailer can be left at the 5 foot setback, but that will require the exterior wall to have a one hour fire resistance rating. Please verify. |
06/14/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/14/2018 | EHAMBLI1 | ENGINEERING | REVIEW | Passed | |
06/14/2018 | EHAMBLI1 | OIP | REVIEW | Passed | |
06/14/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
06/14/2018 | EHAMBLI1 | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/14/2018 | SVALENZ1 | OUT TO CUSTOMER | Completed |