Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM04532
Parcel: 11504498B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM04532
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Show the location on the new Temporary service 'A' and downstream associated equipment on the site plan. Ref: City of Tucson, Commercial Plan Submittal Requirements, 2012 IBC sec 107.2.1, 2011 NEC.
06/14/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Per the IBC Table 602, the new trailer must be located a minimum distance of 10 feet from the property line. The exterior wall will then require no fire resistance rating. The trailer can be left at the 5 foot setback, but that will require the exterior wall to have a one hour fire resistance rating. Please verify.
06/14/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/14/2018 EHAMBLI1 ENGINEERING REVIEW Passed
06/14/2018 EHAMBLI1 OIP REVIEW Passed
06/14/2018 MARTIN BROWN FIRE REVIEW Approved
06/14/2018 EHAMBLI1 ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/14/2018 SVALENZ1 OUT TO CUSTOMER Completed