Permit Number: T18CM04277
Parcel: 13824023J

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T18CM04277
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/09/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
11/09/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the civil plans referenced on sheets P1.1 and P1.2. An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). An 11"x17" reference copy is insufficient; provide a full-size civil plan as part of the construction documents. Reference: Sections 104.2 and 107.2.1, IBC 2012.
11/09/2018 ROBERT SHERRY WATER REVIEW Reqs Change An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). Provide a site plan showing the installation of the water service to the building and the installation of the building sewer. An 11"x17" reference copy is insufficient; provide a full-size civil plan as part of the construction documents. Reference: Sections 104.2 and 107.2.1, IBC 2012. [Initial comment: Provide the civil drawings that show the location and size of the proposed water meter and backflow prevention assembly.]
11/19/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Plan Sheet E1.1, E1.2. The Existing 'XA' and 'XB' pole mounted luminaires and any other existing exterior lighting must be included in the lumen calcs. Also include them in the site plan along with the new luminaires. Section 104.2(1), Tucson/Pima County Outdoor Lighting Code.
11/21/2018 JOHN VAN WINKLE ENGINEERING REVIEW Approved
11/21/2018 DAVID RIVERA ZONING REVIEW Approved
11/21/2018 DAVID RIVERA ZONING HC REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/28/2018 QJONES1 APPROVAL SHELF Completed
11/28/2018 QJONES1 OUT TO CUSTOMER Completed
11/28/2018 QJONES1 REJECT SHELF Completed