Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T18CM03525
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/10/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Specify stairs as existing for the exit door from the office. Indicate where stairs terminate for the office exit access. 2. The decorative stairs on keynote #6 lead to a window location; specify of part of the exit access. 3. Specify where existing restroom facilities are located; they must be under the tenant occupant or common use. 4. Specity where drinking fountain is located. 5. Accessibility is required if the office space is used for the provision of goods or services. 6. Indicate the floor level of the tenant improvement and the uses of the adjacent spaces. 7. Provide details of the guard rail at the roof mechanical unit; elevations, height and attachment of the rail to the roof deck. 8. Indicate if there are changes to the structural sheet that was approved. |
| 07/10/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Designate a circuit and panel designation for the HP-P1 mechanical unit on the roof. Update load calcs accordingly . NEC 408.4. |
| 07/10/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide cooling/heating load calculations for the new AC unit. 2. The condensate for the new AC unit terminates over an existing roof drain; where does the roof drain terminate? 3. Provide a detail of the proposed guard rail to show that the gaurd rail complies with the requirements of Section 304.11, IMC 2012. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/16/2018 | KROBLES1 | OUT TO CUSTOMER | Completed |