Permit Number: T18CM02827
Parcel: 129043530

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T18CM02827
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2018 MARTIN BROWN FIRE REVIEW Approved
05/04/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S1; General Structural Notes (Foundations): For the pier footing, add to the note the allowable end bearing pressure, the skin friction, and revise the lateral bearing capacity (per the Geotechnical Evaluation Report 2923JH080-G).
2. Sheet S4; Spread Footing Schedule: The schedule indicates 6-#6 and 11-#6 footing reinforcement, while the calculations indicate 12-#6 and 22-#6. Please coordinate.
05/07/2018 STEVE SHIELDS ZONING REVIEW Passed
05/07/2018 SSHIELD1 ENGINEERING REVIEW Passed
05/15/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved