04/26/2018 PIMA COUNTY BUILDING-RESIDENTIAL REVIEW Reqs Change T18CM02491 – PERMIT REVIEW COMMENTS
Reviewer: Chris Anderson
Date: April 26, 2018
BUIILDING - RESIDENTIAL
The prescriptive roof insulation must be minimum R-38. Keynote 4 on sheet A3.1 shows roof insulation as R-19. Ref. 2012 IRC Table N1102.1.1.
Drawings indicate that new exterior walls will be Mikey Block ICF wall system. Submit manufacturer’s data showing typical construction details. Ref. 2012 IRC R106.1.
Drawings indicate that new exterior walls will be Mikey Block. Submit manufacturer’s data showing tested R-values for this wall assembly and note R-value in the drawings. Ref. 2012 IRC N1102.1.
In lieu of complying with the prescriptive R-values for exterior envelope (comments 1 and 3 above) submit a passing REScheck for the building envelope listing the wall and roof assemblies, fenestration and associated R-values stated in the documents. The REScheck components must match the components shown in the drawings.
On sheet A2.1 identify the bottom line to which vertical dimensions are started as “finish floor line.” Ref. 2012 IRC R106.1.
Indicate roof slopes for new addition on elevations, sheet A2.1. Ref. 2012 IRC R106.1.
An unused keynote “X” is shown for the sliding patio doors on south elevation, sheet A2.1. Use this marker as keynote 15 and indicate that the maximum U-factor shall be 0.40 and max. SHGC for this door shall be 0.25. Ref. 2012 IRC Table N1102.1.1.
Footing F-1 height and reinforcing in the Footing Schedule, sheet S1.1, do not match what is shown on details 1 and 2 this sheet.
On details 1 and 2/S1.1 show the ground line and add a 1’-0” dimension from grade to bottom of footing. Ref. 2012 IRC R403.1.4.
On detail 1/S2.1 the anchor bolt holding the top plate to top of ICF wall is shown extending into the Styrofoam Mikey Block. Submit Mikey Block manufacturer’s recommended anchorage detail for wood top plates. Ref. 2012 IRC R106.1.
On sheet S2.1, Beam Schedule, beam B-1 is referenced with a -. Is it intended that these lintels be ICF as shown on Typical Lintel Detail A? If so, reference this detail in the Beam Schedule.
The ICF lintel detail references the 2000 IRC which has not been used in the City of Tucson since January 2004. Revise to 2012 IRC. Also change the referenced code section to R611.8.2.
Typical Lintel Detail note 3 cannot be met with the current design. Per 2012 IRC Figure R611.8(1) the minimum height of screen-grid ICF wall systems is 12”. The south elevation on sheet A2.1 shows the lintels over the 6’-0” wide door and window openings as substantially less than 12”. Complying with the prescriptive Code would require that top of window and door frame be located 6’-0” above the floor based on the 7’-0” dimension given on the west building elevation, sheet A2.1. Please explain how you will achieve top of masonry opening at 6’-8” as shown on the south elevation.
Regarding detail 1/S2.1, revise to comply with prescriptive Figure R611.9(9) and associated Table R611.9(9). Ref. 2012 IRC R611.9.3(1). J-bolts shall not be used per R611.9.1.1 with this detail and be aware that maximum spacing for anchor bolts is 24” per Table R611.9(9).


MECHANICAL - RESIDENTIAL
The mechanical plan show mini-split heat pumps throughout the remodeled dwelling and new addition. Show how condensate from each indoor unit will be routed to the exterior.
On the mechanical plan please indicated how a whole house ventilation system will be provided/controlled to accommodate requirements of 2012 IRC M1507.3.
PLUMBING - RESIDENTIAL
Water heater detail on sheet P1.1 indicated “ASME rated P.T. relief to daylight” and “1” drain to daylight” for the pan. How will you accomplish this with this interior water heater?
ELECTRICAL - RESIDENTIAL
On electrical sheet E1.1 provide outdoor lighting lumen calculations per Outdoor Lighting Code Table 401.1 for lighting area E3.
On the electrical plan, sheet E1.1, indicate carbon monoxide alarms outside each sleeping area in the immediate vicinity of bedrooms. Ref. 2012 IRC R315.