Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2018 JPEELDA1 FIRE REVIEW Approved
04/23/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Exits are not allowed to pass through kitchens or stock rooms. The occupant load exceeds 50 persons therefore a minimum of 2 exits are required. IBC 1014.2 item 4.
2. Show maneuvering clearances in ADA restrooms. A117.2.1-304.3
3. Remove reference to the California Building Code from the referenced code on GENERAL STRUCTURAL NOTES. IBC 107.2.1
4. Cite the correct seismic design category for the City of Tucson on the GENERAL STRUCTURAL NOTES.
5. Correct the edition of the IBC to the 2012 edition on SPECIAL INSPECTIONS. IBC 1704.1
04/25/2018 ERIC NEWCOMB MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Submit verification that the cooling and heating duct system is sized in accordance with a nationally recognized standard such as ASHRAE, ACCA or equal.
2. Provide heating and cooling calculations to verify the size and capacities of the new AC 1. : Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012
04/25/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Provide verification of compliance to the City of Tucson lighting ordinance for all exterior wall and pole mounted luminaries.
04/25/2018 GPERU1 WATER REVIEW Approved
04/25/2018 ERIC NEWCOMB PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for at least 10-seconds for accessibility. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Verify that all three compartments of the 3-compartment sink are indirectly drained to the new floor sink and are independent of each other. Reference: Sections 801.2 and 802.1.8, IPC 2012.
3. Floor drains in the kitchen are required to drain through the grease trap; revise drain pipe layout. Section 1003.3 (A), IPC 2012 as amended by the City of Tucson.
04/30/2018 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: Jack in the Box - 3326 E. Grant
T18CM02242
Building Plan (1st Review)

TRANSMITTAL DATE: April 30, 2018

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Keynote 32 calls out for a "NEW ACCESSIBLE PATH OF TRAVEL TO THE EXISTING PUBLIC WAY". It is not clear how access is provide to the existing sidewalk that runs along the north side of the building, is there a ramp or is the concrete flush with pavement.

3. As the proposed accessible path encroaches into the existing exit access aisle provide a width dimension for the access aisle.

4. Provide a note on the plan stating that all accessible route slopes are to comply with ICC A117.1, Section 403.3; 5% maximum running slopes and 2% maximum cross slopes.

5. Detail 6, sheet SD2.1 does not match what is shown on the plan.

6. Until all other PDSD review agencies have approved the building plans zoning cannot approve.

Once the above comments are addressed Zoning will provide an over-the-counter review. Please call or email to schedule an appointment for this review.