Permit Number: T18CM02157
Parcel: 114516790

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T18CM02157
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
03/22/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide hot water for the service sink. Reference: Section 607.1, IPC 2012.
03/22/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/22/2018 ROBERT SHERRY WATER REVIEW Completed
05/04/2018 MCASTRO2 ZONING REVIEW Approved
05/04/2018 MCASTRO2 ENGINEERING REVIEW Passed
05/30/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/30/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Per the Outdoor Lighting Code exception 102.4.2, the luminaires (K3) cannot exceed 2000 lumens each. The lumens shown per the lighting schedule exceed 2000 lumens.
05/30/2018 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/31/2018 QJONES1 APPROVAL SHELF Completed
05/31/2018 QJONES1 OUT TO CUSTOMER Completed
05/31/2018 QJONES1 REJECT SHELF Completed