Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T18CM02157
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/22/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 03/22/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide hot water for the service sink. Reference: Section 607.1, IPC 2012. |
| 03/22/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 03/22/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/04/2018 | MCASTRO2 | ZONING | REVIEW | Approved | |
| 05/04/2018 | MCASTRO2 | ENGINEERING | REVIEW | Passed | |
| 05/30/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/30/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Per the Outdoor Lighting Code exception 102.4.2, the luminaires (K3) cannot exceed 2000 lumens each. The lumens shown per the lighting schedule exceed 2000 lumens. |
| 05/30/2018 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/31/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 05/31/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 05/31/2018 | QJONES1 | REJECT SHELF | Completed |