Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T18CM02149
Parcel: 12310001C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM02149
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Check the addition of the roof drainage areas. One section of both the primary stormwater conductors and the overflow stormwater conductors are too small for the design flow (see mark-up on M2.2.P). [Second comment: Where is the slope noted on the drawing?] [Initial comment: State the minimum slope for the stormwater conductors. Reference: Section107.2.1, IBC 2012.]