Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM02149
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/29/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Check the addition of the roof drainage areas. One section of both the primary stormwater conductors and the overflow stormwater conductors are too small for the design flow (see mark-up on M2.2.P). [Second comment: Where is the slope noted on the drawing?] [Initial comment: State the minimum slope for the stormwater conductors. Reference: Section107.2.1, IBC 2012.] |