05/10/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comments 5 and 7 were not corrected as required. |
05/10/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | A hole in the collector box does not qualify as a secondary roof drain. Section 1108.2, IPC 2012 requires a secondary roof drain to provide a flow rate equivalent to the primary roof drain even if the primary drain is completely blocked. In addition, a secondary drain requires a separate point of discharge from the primary roof drain. [Initial comment: Provide secondary (overflow) roof drainage. Reference: Sections 1101, 1106 and 1108, IPC 2012, and Sections 1611.1 and 1611.3, IBC 2012.] |