Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T18CM00811
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/07/2018 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T18CM00808 Duplex Bldg. 1, T18CM00809 Duplex Bldg. 2, T18CM00810 Duplex Bldg. 3 and T18CM00811 SFR Building 4 New Multi-Family Development Residential Building Plans (1st Review) Buildings 1. 2, 3, 4 348 E Elvado Road - R-2 Zone TRANSMITTAL DATE: February 7, 2018 DUE DATE: February 14, 2018 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the building plans for building 1, 2, 3, and 4 but cannot approve them at this time. The development package related to this development was not available for reference or comparison with the building plans as it relates to the zoning review purview, which includes the building square footage, building height, building footprint, and location on the site. 2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP. (Include as a reference copy of the most current or the approved and PDSD stamped version of the DP with the next building submittal.) 3. COMMENT: If any changes are necessary, due to the PDSD Residential Plan Reviewer's comments that affect or change the building footprint, height, or square footage, or location the DP will need to be updated prior to approval of the building plans by Zoning. 4. COMMENT: Once the plans have been reviewed and approved by the Residential Plan Reviewer and zoning has verified consistency with the DP, the building plans can be approved by zoning. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans and reference copy of the most current or approved version of the DP. |
| 02/07/2018 | DAVID RIVERA | NPPO | REVIEW | Passed | |
| 02/16/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 03/01/2018 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T18CM00811 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL COMMENTS: 1. Update the Project Area totals on sheet C1.0. 2. Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc. 3. All SFR and Duplex plans submitted after July 1, 2009 require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549 with the following provisions: 1. A 4 square feet area for (meter, disconnect & inverter) equipment adjacent to the electrical service panel or near the proposed collector panel space. 2. The best roof space available for accommodating PV solar collector panels with capacity for collector dead loading (typically 4 lbs/SF). 3. A minimum 3,800 volt-ampere PV electrical load entry on the Service Load Calculation (Show as a continuous load of 15.8 A). 4. An Electrical Panel Schedule with a 240 volt circuit breaker space labeled "reserved for Photo Voltaic". See electrical comments. 4. All construction drawings submitted after June 1, 2010 for one- or two-family dwellings must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. Include two clothes washer standpipes at an exterior wall, one with an above grade stub-out, and one plumbed to the building drain. SITE PLAN: 1. Indicate the location of buildings, utility meters and gas, water, electric and sewer lines from property line to building, R106.1.1. Show the point of connection of proposed lines to the service lines for verifying correct sizes and necessary upgrades. FLOOR PLANS: 1. Show a maximum ½" floor elevation change at a notated accessible route entrance on the floor plan, R106.1.1. Include the threshold condition at the vehicle doorway or an exterior hinged door when the garage is used for the accessible route. SECTIONS - DETAILS: 1. Show exterior wood siding, sheathing and wall framing with a 6" clearance above the ground (R317.1 item 5). Update detail #9/A7.0. PLUMBING PLANS: 1. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Update the sizes shown on the plan for consistency with correct sizes shown on the isometric diagram sheet P1.1. MECHANICAL PLANS: 1. Provide (an HVAC system with) whole-house mechanical ventilation with continuous or a minimum controlled intermittent airflow rate, R303.4 & M1507.3. Show a source of outside supply air or continuous exhaust fan function. ELECTRICAL PLANS: 1. Show or notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315. 2. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, R4002.14. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
| 03/02/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | Floodplain use permit required |