Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18BU00593
Parcel: 11504498B

Review Status: Completed

Review Details: POOL - COMM MODEL

Permit Number - T18BU00593
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change Please provide the requested information and/or changes to the plans.
1. Provide structural calculations and details for verification that the existing roof and building structural components are able to support the pool and all associated equipment.
2. Provide structural framing details that show the construction of the pool and attachment tot he existing roof structure.
3. The structural calculations for the pool shell need to reflect that the pool is being installed on top of a roof structure and not shown as in-ground.
4. Show the pool barrier type and all doors that lead onto the pool area for conformance to AZ STATE barrier requirements.
10/24/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/24/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1.Correct the sediment trap shown on detail 10/SP503 per Section 408.4, IFGC 2012.
2. Provide reference drawings showing the installation of drains "by others" (e.g. backwash sump, planters, pool sub-drains).
10/24/2018 AHINES2 ENGINEERING REVIEW Passed
10/24/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/24/2018 ALEXANDRA HINES ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/10/2018 QJONES1 APPROVAL SHELF Completed
12/10/2018 QJONES1 OUT TO CUSTOMER Completed
12/10/2018 QJONES1 REJECT SHELF Completed