Permit Number: T18BU00300
Parcel: 12407140A

Review Status: Completed

Review Details: POOL - COMM MODEL

Permit Number - T18BU00300
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1 Provide a complete electrical plan showing all grounding, electrical equipment lay-out, branch circuit, panel designations for all equipment, locate the pool panel and provide a complete panel schedule including load calcs.
#2 Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code for exterior lighting.
Ref: 2012 IBC sec 107.2.1, 2011 NEC, 2012 Outdoor Lighting Code.
05/14/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide coordination drawings showing how and where the pool mechanical room is located.
2. Show how the three pool heaters are vented.
05/14/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide coordination drawings for the pool plumbing and the building plumbing (e.g. gas piping, sanitary drains).
05/14/2018 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change Provide plans showing how pool drains connect to building drainage system (See Plumbing Comments)

John Van Winkle
john.vanwinkle@tucsonaz.gov
520-837-5007
05/14/2018 KELLY LEE ZONING REVIEW Passed
10/11/2018 AVAUGHN1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/11/2018 AVAUGHN1 APPROVAL SHELF Completed
10/11/2018 AVAUGHN1 OUT TO CUSTOMER Completed
10/11/2018 AVAUGHN1 REJECT SHELF Completed