Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM09232
Parcel: 117142140

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T17CM09232
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2019 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change BUILDING – COMMERCIAL
1. The revision list of drawings has a note “Public Building Deleted from Scope of this Permit.” However the revised structural, mechanical, plumbing and electrical sheets submitted for review all include revision work to the public buildings nos. 6 and 7. All work for the public buildings shall be removed from the Revision 2 documents so that they reflect only the revisions to buildings 2, 3, 4 and 5.
2. Architectural drawings bearing the Architect’s seal and reflecting the modifications to buildings 2 – 5 (clouded) shall be included with the revised engineering drawings.
01/18/2019 MARTIN BROWN FIRE REVIEW Approved
01/18/2019 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLUMBING – COMMERCIAL
1. The revision list of drawings has a note “Public Building Deleted from Scope of this Permit.” However the revised structural, mechanical, plumbing and electrical sheets submitted for review all include revision work to the public buildings nos. 6 and 7. All work for the public buildings shall be removed from the Revision 2 documents so that they reflect only the revisions to buildings 2, 3, 4 and 5
01/18/2019 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL – COMMERCIAL
1. The revision list of drawings has a note “Public Building Deleted from Scope of this Permit.” However the revised structural, mechanical, plumbing and electrical sheets submitted for review all include revision work to the public buildings nos. 6 and 7. All work for the public buildings shall be removed from the Revision 2 documents so that they reflect only the revisions to buildings 2, 3, 4 and 5
01/22/2019 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL – COMMERCIAL
1. The revision list of drawings has a note “Public Building Deleted from Scope of this Permit.” However the revised structural, mechanical, plumbing and electrical sheets submitted for review all include revision work to the public buildings nos. 6 and 7. All work for the public buildings shall be removed from the Revision 2 documents so that they reflect only the revisions to buildings 2, 3, 4 and 5.
02/05/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T17CM09232, T17CM09233, T17CM09234, T17CM09235, - Building plan revisions
Building Plan Review (2nd Revision Review) Hotel Guest Rooms and Public Building
485 S. Stone Avenue - C-3 Zoning

TRANSMITTAL DATE: February 4, 2019

DUE DATE: February 8, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Zoning has done a review of the revisions to the building plans. While the revisions do not affect zoning requirements zoning cannot approve the plans until the 2nd Party plans reviewers approve the revisions.

2. COMMENT: Zoning will review the building plans on the next submittal to assure that any revisions are consistent with the approved DP and do not affect any zoning requirements already approved. If any changes are necessary that involve changes to the exterior of the buildings that affect zoning requirements the DP will have to be revised to reflect the changes.


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans
02/05/2019 DAVID RIVERA DESIGN PROFESSIONAL REVIEW Passed
02/07/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T17CM09232

1) Engineering can conduct an over the counter approval of the building plan modifications once any outstanding commercial review comments have been addressed

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007

Final Status

Task End Date Reviewer's Name Type of Review Description
03/12/2019 AMARTIN1 OUT TO CUSTOMER Completed