Permit Number: T17CM08215
Parcel: 12212039C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM08215
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/20/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. A written response was not included in the resubmittal.
#2. As requested per the last plan review comments, there was no compliance with comment 'B' and 'C'.
Ref: 2012 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code.
04/18/2018 BLARSON1 ZONING REVIEW Approved APPROVED BY MIKE MORENO