Permit Number: T17CM08215
Parcel: 12212039C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM08215
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 21; Sheet A2.1; East Elevation: There is one detail on the East Elevation that has not changed from the previous 3/A8.1. Please revise.
2. Previous Comment 24; Sheet A9; Floor Plan 4: Please indicate the walls on the plan that extend only 6" above the ceiling at the shaft north of the elevator, and reference Detail 1/A3 at those walls.
3. Previous Comment 25; Sheet A9; Floor Plan 1: Please indicate the walls on the plan that extend only 6" above the ceiling at the shaft south of Stair 1 (and at two other locations in Gallery 211 on Sheet A1.3), and reference Detail 1/A3 at those walls.
4. Previous Comment 26; Drinking Fountains: Please indicate on Sheet A1.2 the location of the single point of use water dispensers, and reference Sheet P1.2 for specific information.
5. General: Please provide written responses to all review comments.
02/16/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/21/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: Steve Shields
Principle Planner

PROJECT: Royal Service Building @ 4984 E. 22nd Street
T17CM08215
Building Plan (2nd Review)

TRANSMITTAL DATE: February 21, 2018

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Until development package DP17-0285 is approved the service building plans cannot be approved.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
02/22/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/01/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Per the last electrical plan review, it was requested to provide full compliance with the Tucson/Pima County Outdoor Lighting Code. The "Outdoor Lighting Calculation" table included in this submittal is incorrect due to incomplete lumen calcs or other incorrect information as follows:
(a) Per the cover Plan Sheet T1. The parcel size is 6.34 acres. Not 2.7 acres, as stated on the provided Lighting Calcs, plan sheet ES101. Consequently a site plan of the existing luminaire locations and inventory was not provided on the site plan or in the lumen calcs in this submittal. Section 104.2.1
(b) Verify that the lamp color temperature for the new luminaires installed in the areas not classified as "Special Use Areas" complies with the 3500K limit per section 402.1. Also see section 701.2.
(c) Not all areas on the parcel qualify as "Special Use Areas". For example, areas used for storage, maintenance, carwash or detail areas, employee parking, office area exterior lighting not used exclusively to show vehicles for sale.
(d) When Lumen calcs are completed, verify whether or not a special inspection is required. Section 104.2.2.
Ref: 2012 IBC sec, 107.2.1, 2011 NEC, Tucson/Pima County Outdoor lighting Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/20/2018 QJONES1 APPROVAL SHELF Completed
03/20/2018 QJONES1 OUT TO CUSTOMER Completed
03/20/2018 QJONES1 REJECT SHELF Completed