Permit Number: T17CM07755
Parcel: 125121110

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM07755
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2017 MCASTRO2 ZONING REVIEW Approved
10/16/2017 ROBERT SHERRY WATER REVIEW Completed
10/16/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide load calcs for the panels.
#2. Indicate conduit, conductor sizes, fuse sizes and types for the AC units, water heater, and branch circuits. Provide for disconnecting means. See note #5 of the electrical spec's.
#3. Indicate circuit and operation (control) of the restroom exhaust fan.
Ref; 2012 IBC sec. 107.2.1, 2011 NEC.
10/16/2017 MCASTRO2 ENGINEERING REVIEW Passed
10/16/2017 TPROBAS1 BUILDING-COMMERCIAL REVIEW Completed
10/16/2017 MARTIN BROWN FIRE REVIEW Approved
10/16/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/16/2017 TPROBAS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/17/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed