Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM07755
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/16/2017 | TPROBAS1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/16/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 10/16/2017 | MCASTRO2 | ENGINEERING | REVIEW | Passed | |
| 10/16/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide load calcs for the panels. #2. Indicate conduit, conductor sizes, fuse sizes and types for the AC units, water heater, and branch circuits. Provide for disconnecting means. See note #5 of the electrical spec's. #3. Indicate circuit and operation (control) of the restroom exhaust fan. Ref; 2012 IBC sec. 107.2.1, 2011 NEC. |
| 10/16/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/16/2017 | TPROBAS1 | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 10/16/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/16/2017 | MCASTRO2 | ZONING | REVIEW | Approved | |
| 10/17/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |