Permit Number: T17CM07725
Parcel: 12112399J

Address:
5302 E PIMA ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM07725
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2017 ALEXANDRA HINES ZONING REVIEW Approved
10/12/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/12/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/12/2017 AHINES2 ENGINEERING REVIEW Passed
10/12/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review 1. Sheet A1.0; Dimensioned Floor Plan: On the east side of the pool, the 2'-6" wide egress path does not meet the requirements of the IBC Table 1018.2. Please revise.
2. Sheet A1.0; Dimensioned Floor Plan: Please indicate the accessible lift on the plan. Provide specifications/cut sheets for this lift.
3. Sheet A1.0; Typical Wood Interior Wall: A note indicates to see the plan for stud widths. That was not located on the plan. Please verify.
4. Sheet A1.1; Electric Water Cooler: The floor plan indicates a high/low drinking fountain. The detail on Sheet A1.1 indicates a single drinking fountain. Please revise per the ICC/ANSI Section 602.
5. General: Please provide structural calculations and details (on a full sized sheet) for the pool. If this is a deferred submittal, please indicate on the drawings.
6. General: What was the previous use of this space? Please indicate on the drawings. Will this be a change of use?
7. General: Please provide written responses to all review comments.
10/12/2017 ROBERT SHERRY WATER REVIEW Completed
10/12/2017 ARUIZ1 PLUMBING-COMMERCIAL REVIEW Needs Review
10/12/2017 MARTIN BROWN FIRE REVIEW Approved
10/12/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review