Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM07617
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/09/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/09/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 10/09/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/09/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Please indicate New or Existing for all electrical equipment. Also equipment on the panel schedule. #2. The riser diagram shows 200 amp service equipment and the floorplan shows 400 amp. Is it over head or underground fed from the utility. Please clarify. #3. The panel schedule shows the electrical panel marked as 'A'. the electrical devices and equipment are designated to panel 'CA'. Please clarify. #4. How is the emergency lighting circuited? #5. Provide compliance with the 2012 IECC for lighting. #6. Provide a complete luminaire schedule. #7. Adopted electrical code is the 2011 NEC not 2012. (cover sheet). FEE'S INCOMPLETE Ref: 2012 IBC 107.2.1, 2011 NEC |
| 10/09/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/09/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/13/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 10/17/2017 | KROBLES1 | ENGINEERING | REVIEW | Passed | |
| 10/17/2017 | KROBLES1 | ZONING | REVIEW | Approved | MGAYOSSO |