Permit Number: T17CM07617
Parcel: 133290060

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM07617
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/09/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/09/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Please indicate New or Existing for all electrical equipment. Also equipment on the panel schedule.
#2. The riser diagram shows 200 amp service equipment and the floorplan shows 400 amp. Is it over head or underground fed from the utility. Please clarify.
#3. The panel schedule shows the electrical panel marked as 'A'. the electrical devices and equipment are designated to panel 'CA'. Please clarify.
#4. How is the emergency lighting circuited?
#5. Provide compliance with the 2012 IECC for lighting.
#6. Provide a complete luminaire schedule.
#7. Adopted electrical code is the 2011 NEC not 2012.
(cover sheet).
FEE'S INCOMPLETE
Ref: 2012 IBC 107.2.1, 2011 NEC
10/09/2017 MARTIN BROWN FIRE REVIEW Approved
10/09/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/09/2017 ROBERT SHERRY WATER REVIEW Completed
10/13/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/17/2017 KROBLES1 ENGINEERING REVIEW Passed
10/17/2017 KROBLES1 ZONING REVIEW Approved MGAYOSSO