Permit Number: T17CM06552
Parcel: 117120310

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM06552
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2017 ENEWCOM1 WWM REVIEW Passed
08/25/2017 ENEWCOM1 WATER REVIEW Passed
08/25/2017 JVINCEN1 FIRE REVIEW Approved
08/25/2017 ERIC NEWCOMB PLUMBING-COMMERCIAL REVIEW Passed
08/25/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/25/2017 ERIC NEWCOMB MECHANICAL-COMMERCIAL REVIEW Passed
08/25/2017 ACONNOR1 ENGINEERING REVIEW Passed
08/25/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide branch circuit and panel designations for the new lighting and receptacles.
Locate the electrical panel on the floorplan.
Provide a complete panel schedule.
Provide a luminaire schedule or cut sheet for the lighting. REf; 2012 IBC 107.2.1. 2011 NEC.
08/25/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; Floor Plan 5: At the new stud wall note, please indicate the stud size and spacing. In addition, indicate the top of the wall bracing as required.
2. Sheet A1.0; Section 3: The new metal awning (by owner) must include details of how the awning attaches to the walls. Please provide.
3. Sheet A1.0; Section 3: A note indicates to see structural for the new storefront entry. No information or details were located. Please verify.
08/25/2017 ANDREW CONNOR ZONING REVIEW Approved