Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW - COMMERCIAL TI
Permit Number - T17CM06203
Review Name: 3RD PARTY REVIEW - COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/24/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/24/2017 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. The water calculations indicate a demand of 80 GPM using an existing 1-1/2" water meter. Tucson Water limits 1-1/2" water meters to maximum demand of 75-GPM. Provide a letter from Tucson Water that allows the use of a 1-1/2" water meter to be used for this project. 2. The water calculations do not show any pressure loss for a reduced pressure backflow prevention assembly. Show the location of the reduced pressure backflow prevention assembly on the drawings; indicate the size of the assembly and include it's pressure drop in the water calculations. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf. |
| 09/12/2017 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 09/15/2017 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Completed | |
| 09/15/2017 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 09/15/2017 | KROBLES1 | 3RD PARTY REVIEW-COMMERCIAL | AT 3RD PARTY OFFICE | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/15/2017 | KROBLES1 | OUT TO CUSTOMER | Completed |