Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM05355
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/13/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 07/13/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide listing information for the clothes dryer to show that the proposed dryer exhaust duct is sized correctly. Reference: Sections 304.1 and 504.6.1, IMC 2012. 2. Provide signage indicating the total equivalent length of the concealed dryer exhaust duct. Reference: Section 504.6.5, IMC 2012. |
| 07/13/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/13/2017 | ACONNOR1 | ENGINEERING | REVIEW | Passed | |
| 07/13/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter (see unit 'A'). Reference: Section 406.2, IPC 2012. 2. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 604.9, IPC 2012. 3. Explain how the shut off valves for the washer are accessible. Reference: Section 606.3, IPC 2012. |
| 07/13/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/17/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/01/2017 | ARUIZ1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 08/01/2017 | ARUIZ1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 08/01/2017 | ARUIZ1 | WWM | REVIEW | Needs Review |