Permit Number: T17CM05355
Parcel: 13324006E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05355
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2017 ANDREW CONNOR ZONING REVIEW Approved
07/13/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide listing information for the clothes dryer to show that the proposed dryer exhaust duct is sized correctly. Reference: Sections 304.1 and 504.6.1, IMC 2012.
2. Provide signage indicating the total equivalent length of the concealed dryer exhaust duct. Reference: Section 504.6.5, IMC 2012.
07/13/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/13/2017 ACONNOR1 ENGINEERING REVIEW Passed
07/13/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter (see unit 'A'). Reference: Section 406.2, IPC 2012.
2. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 604.9, IPC 2012.
3. Explain how the shut off valves for the washer are accessible. Reference: Section 606.3, IPC 2012.
07/13/2017 ROBERT SHERRY WATER REVIEW Completed
07/17/2017 MARTIN BROWN FIRE REVIEW Approved
08/01/2017 ARUIZ1 BUILDING-COMMERCIAL REVIEW Needs Review
08/01/2017 ARUIZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/01/2017 ARUIZ1 WWM REVIEW Needs Review