Permit Number: T17CM04982
Parcel: 11712099A

Address:
20 S STONE AV

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T17CM04982
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2017 MARTIN BROWN FIRE REVIEW Approved
09/28/2017 ROBERT SHERRY WATER REVIEW Completed
10/05/2017 LOREN MAKUS ENGINEERING REVIEW Reqs Change DP must be approved first.
10/10/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: 20 S. Stone Ave
T17CM04982
Building Plan (2nd Review)

TRANSMITTAL DATE: October 10, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Until the revisions to development package DP16-0200 are approved the building plans cannot be approved.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
10/23/2017 GERRY KOZIOL WWM REVIEW Reqs Change THE FOLLOWING IS NEEDED FOR SEWER CONNECTION FEE APPLICATION APPROVAL:

NEED TYPE lll CAPACITY REVIEW RWRDCAPACITYRESPONSE@PIMA.GOV - 520-724-6642

NEED TO CLARIFY WATER METER SIZE:
TWO 2" WATER METERS PER DRAWING P101
ONE 3" WATER METER PER DRAWING P201

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2018 QJONES1 APPROVAL SHELF Completed
03/21/2018 QJONES1 OUT TO CUSTOMER Completed
03/21/2018 QJONES1 REJECT SHELF Completed