Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM04810
Parcel: 13213079A

Address:
3025 S KINO PW

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM04810
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/14/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/14/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/21/2017 KELLY LEE ZONING REVIEW Approved x
09/29/2017 KLEE1 ENGINEERING REVIEW Passed
09/29/2017 GERRY KOZIOL WWM REVIEW Approved