Permit Number: T17CM04810
Parcel: 13213079A

Address:
3025 S KINO PW

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T17CM04810
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2017 MARTIN BROWN FIRE REVIEW Approved
06/23/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: Discount Tire - Tucson Market Place
T17CM04810
Building Plan (1st Review)

TRANSMITTAL DATE: June 23, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. It appears that the proposed building plans match development package DP17-0056 but until the development package is approved Zoning cannot approve the building plans.

3. The development package sheets provided in the building plan set will either need to be the signed approved development package sheets, marked as 'REFERENCE ONLY", or removed from the building plans.

4. Sheet A2.1 detail 9 calls for truncated domes, for your information truncated domes are only required within the public right-of-way and on raised platforms not on accessible ramps on site.

5. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
07/05/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012.
2. Coordinate the number, location, and type of electric unit heaters with those shown on the architectural drawings. Reference: Section 107.2.1, IBC 2012.
3. Provide information on the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012.
07/05/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide automatic faucets for the restroom lavatories. The faucets shall dispense a maximum of 0.25 gallons per metering cycle. For accessibility, verify that the cycle time of the faucet is at least 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide an approved vacuum relief valve for the scheduled bottom-fed water heater located above the fixture outlets. Reference: Section 504.2, IPC 2012.
3. The schedule for electrical panel C indicates the provision of a receptacle circuit (C21) for a misting system. Where is the misting system to be located? A misting system will require the installation of a reduced pressure principle backflow prevention assembly. Reference: Section 608.16.6, IPC 2012.
4. Provide a cleanout at the base of each roof drain stack prior to connection to the horizontal storm drain. Reference: Sections 708.3.4 and 1101.8, IPC 2012.
07/05/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0 Sheet Index: Sheet A4 of submitted plans is not included in the index.
2. Sheet A1.0 Project Information Building Area indicates an allowable area of 37,500 sq. ft. per IBC 503. Basic allowable area of 12,500 sq. ft. (IBC Table 503) + 300 percent increase for automatic sprinkler (IBC 506.3) 37,500 = a total allowable area of 50,000 sq. ft. Please revise to reflect correct calculations.
3. Sheet A1.0 Project Information: Please include ANSI A117.1 to the design codes.
4. Sheet A7.2 Detail 20 Viewing Counter: Viewing counter shall be provided with a viewing area which has a maximum counter height of 34 inches for ADA.
5. Sheet S1.1: The City of Tucson requires all lettering, upper and lower case, to be a minimum of 3/32 inch in height. Comment typical all sheets as applicable.
6. Sheet S1.1 Expansion Bolts: Simpson Strong Bolt Report #1771 is no longer valid. Please reference a valid report.
7. Sheet S1.1 Epoxy Anchors: Hilti HY-150 Report #1967 is no longer valid. Please reference a valid report.
8. Provide a Special Inspection Certificate.
9. General: Provide written responses to all comments.
07/05/2017 ROBERT SHERRY WATER REVIEW Completed
07/06/2017 TPROBAS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
07/18/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide complete compliance with the 2012 IECC for lighting.
#2. Provide complete compliance with the Tucson/Pima County Outdoor lighting Code. Can be downloaded from www.tucsonaz.gov/pdsd.
#3. Verify that all the lighting is included in the service bay areas.
Ref: 2012 IBC sec. 107.2.1, 2011 NEC, Tucson Pima County Outdoor Lighting Code.
07/19/2017 LOREN MAKUS ENGINEERING REVIEW Reqs Change DP must be approved first.
07/21/2017 GERRY KOZIOL WWM REVIEW Reqs Change Need for Sewer Connection Fee Application Approval:

PCRWRD/IWC/ Steven Valencia review & approval for installation of oil/sand interceptor per utility plan UT1 and plumbing drawings – 520-724-6200 - steven.valencia@pima.gov).

Final Status

Task End Date Reviewer's Name Type of Review Description
08/03/2017 ARUIZ1 OUT TO CUSTOMER Completed