Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM04421
Parcel: 14043013B

Review Status: Active

Review Details: COMMERCIAL - NEW

Permit Number - T17CM04421
Review Name: COMMERCIAL - NEW
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2017 MARTIN BROWN FIRE REVIEW Approved
06/06/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/06/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide sealed and signed electrical plans by an Arizona Electrical Registrant.
#2. The electrical plan one-line diagram E1.SA.
(a) Shows 2 'temp ses -1'. Do you really want them to have the same nomenclature .Please clarify.
(b) The power requirements for the Guard Shack are not shown.
(c) Identify the construction trailers on the electrical site plan.
(d) Feeder #4 is not shown on the feeder schedule. XXXX ?
(e) Provide complete load calcs.
(f) The feeder sizes and types do not correlate with the ses amp ratings. 1200 amp rated (ses#1) shows 2-sets of 350 mcm, and the 600 amp (ses#1) shows 3- sets of 600 mcm.
(g) The one-line diagram is not complete to the existing PME Switching Cabinet.
(h) Provide for a grounding electrode system to be provided at the SES locations as required per NEC art. 250.32.
Ref: 2012 IBC sec. 107.2.1, 2011 NEC.
06/06/2017 ANDREW CONNOR ZONING REVIEW Approved
06/06/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/06/2017 ROBERT SHERRY WATER REVIEW Passed
06/06/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/06/2017 ACONNOR1 ENGINEERING REVIEW Passed
06/06/2017 ANY COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active
06/06/2017 RSHERRY1 WWM REVIEW Passed No plumbing