Permit Number: T17CM03846
Parcel: 141186030

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM03846
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
As per the previous plan review comment, the reviewer requested information on the plans to provide evidence to the reviewer that the proposed exterior lighting for this project complies with the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE. "#2. Provide complete compliance with the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE, including the flagpole lighting, as outlined per section 104. The Code can be downloaded from www.tucsonaz.gov/pdsd".
The revised exterior lighting calc's is only part of the information required on the plans as outlined in section 104.2.
Additional information needed on the plans:
(a) Parcel size in acres.
(b) Total allowed lumen caps per table 401.1
(c) Indicate Lighting area and option used for calc's.
(d) Provide a complete luminaire schedule that includes the following information, shielding (unshielded or full cut-off), color temperature output, also may include cut sheets by the manufacturer.
(e) Total proposed lighting lumen output for this site, unshielded and full cut-off.
(f) Is a special inspection required, per section 106.2 ?
(g) Compliance with color temperature output, section 402.1.
(h) Curfew requirements for unshielded lighting if applicable, section 403.
(i) Compliance with the lumens allowed and color temperature, Yes or No?
Dansantacruz@tucsonaz.gov
09/07/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed