Review Details: REVISION - - 1ST

Permit Number - T17CM03512
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2017 MARTIN BROWN FIRE REVIEW Approved
06/23/2017 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change BUILDING – COMMERCIAL
Reviewer: Chris Anderson, June 23, 2017
On sheet G0.2, Code Summary under “Building Design Data” states “Area: Unlimited; (507.4) 2 story; 60 foot clear perimeter.” This is incorrect since this building is a 3-story building and IBC article 507.4 pertains only to 2-story buildings. The “interstitial floor” is not a mezzanine and therefore it is a story per definition in 2012 IBC Section 202. Per building area modifications calculations, the maximum allowable area for each story is 109,250 SF. See calculations on returned drawing set. Ref. 2012 IBC 506.1 through 506.3.
Note in Code Summary on sheet G0.2 that this building will be “non-separated occupancies”. Ref. 2012 IBC 508.3.
On plans 1/G1.1 and 1/G1.3 the large offices 1-15 (1st floor) and 1-19 (2nd business floor) all have only 1 exit door. Per occupancy calculation based on IBC Table 1004.1.2 each of these rooms has an occupancy load greater than 49 and therefore require a 2nd means of egress. Ref. 2012 IBC Table 1004.1.2 and Table 1015.1. However, these plans show systems furniture in these rooms which limit the occupancy to less than 50. If Raytheon intends to set up these offices as shown submit a letter from Raytheon indicating that the occupancy for each of these offices will not exceed 49. Ref. 2012 IBC 1004.1.2, exception.
On sheet G2.2, the 2-hour fire-rating of shaft wall assembly “U” appears to be compromised at the steel beam unless proof is submitted that beam will provide a 2-hour fire separation. Ref. 2012 IBC 107.2.1.
On exterior wall sections, sheet A3.31, the wall insulation is indicated to be R-13 batt (cavity) insulation and R-5.6. Prescriptively, insulation for mass walls must be minimum R-6.5 continuous insulation per 2012 IECC Table C402.2 to minimize energy transfer through steel studs. Either revise insulation to comply with minimum prescriptive requirements or submit a building envelope COMcheck for envelope systems shown in plans.
On office plan 1/A4.1 show a 4’-0” minimum clear dimension from door leading edge to wall in vestibule. Ref. ICC/ANSI A117.1-2009 Fig. 404.2.5.
On sheet A5.20, the 2-hour fire-rating of shaft wall assembly appears to be compromised at the steel beam unless proof is submitted that beam will provide a 2-hour fire separation. Ref. 2012 IBC 107.2.1
Submit a door hardware schedule so that egress doors can be checked. Ref. 2012 IBC 107.2.1.
On sheet A6.01 add a boxed note at the door and storefront types “Fixed fenestration shall have a maximum U-value of 0.50, operable fenestrations shall have a maximum U-value of 0.65 and glazed entrance doors shall have a maximum U-value of 0.83. All glazed fenestration shall have a maximum SHGC of 0.25, and opaque swing doors shall have a maximum U-value of 0.61.” Ref. 2012 IECC Tables C402.2 and 403.3. As an alternative to these values, submit a building envelope COMcheck. Ensure that values in the specifications match what is shown on the drawings.
On curtain wall elevations, sheet A6.10, indicate which panels are to be safety glazed. Ref. 2012 IBC 2406.
The lobby front desk elevations on sheet A7.31 indicate two accessible counters 24” long. Per ICC/ANSI A117.1-2009 904.3.1 at least one accessible portion of counter shall be 36” long.
06/23/2017 FRODRIG2 WATER REVIEW Reqs Change WATER – COMMERCIAL
Reviewer: Chris Anderson, June 23, 2017
Please provide site utility sheets in the drawing set as reference showing water meter and backflow preventer sizes and locations.
Revise water calculation footnote 3 on sheet M9.1 to add “…an approved type pressure regulator conforming to ASSE 1003 or CSA B356 preceded by…” Ref. 2012 IPC 604.8.
06/23/2017 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Approved
06/23/2017 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRIC – COMMERCIAL
Reviewer: Charlie Bard, June 23, 2017
Provide electric schedule showing doors that are hard wired with electric strike and specification/cut sheets on electric strike.
06/23/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL – COMMMERCIAL
Reviewer: Chris Anderson, June 23, 2017
Provide heating and cooling load calculations summary sheets that indicate sensible loads for all new heating and cooling units to justify the capacity of selected equipment. Use 104-degrees F summer DB outdoor design temperature with 66-degrees F design wet bulb temperature, and 32-degrees F winter DB outside design temperature per City of Tucson amendment to the 2012 IECC. Please key the mechanical unit designations in the load calculations with the mechanical unit designations in mechanical schedules to avoid comparison errors during review. Ref. 2012 IECC C403.2.1 and C403.2.2. , City of Tucson amendment to the 2012 IECC.
Return air systems with a design capacity greater than 2000 cfm shall be provided with smoke detectors. None appear to be shown in the plans. Ref. 2012 IMC 606.2.1 and 606.2.2.
06/23/2017 FRODRIG2 WWM REVIEW Approved PER CHRIS ANDERSON - PIMA COUNTY
06/26/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: NAE Building 921
T17CM03512
Building Plan (Revision)

TRANSMITTAL DATE: June 26, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Until all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
06/28/2017 LOREN MAKUS ENGINEERING REVIEW Approved